Control - Huawei UPS5000-A-30 User Manual

Hide thumbs Also See for UPS5000-A-30:
Table of Contents

Advertisement

UPS5000-A-30 kVA, 40 kVA and 80 kVA
User Manual
Item
MT
BP/SYSMT
BP/SYSMT switch function
Settings Wizard
When the UPS starts for the first time or restarts after restoring factory settings,
the settings wizard automatically starts.
After first startup, set basic parameters, including the language, date and time,
network parameters, and common parameters.
Restore Default Settings Screen
Restore default settings after the inverter shuts down.

4.2.5 Control

On the Main Menu screen, select Control and press
accessing the Control screen is displayed. The preset password is 000001. After
you enter the password, press
Figure 4-27 Control screen
Starting the Inverter
You can start the inverter manually by pressing Startup.
Issue 13 (2022-01-19)
NO TE
Default settings can be successfully restored only after you set DIP1, DIP2, and DIP3 on the
DIP switch to ON, ON, and OFF respectively.
Copyright © Huawei Technologies Co., Ltd.
Description
Enable or disable PDC maintenance circuit
breaker status detection.
If the BP/SYSMT switch is set to Enable, the
port has dry contact signal access. Using the
port depends on the status of the BP/SYSMT
switch.
If the BP/SYSMT switch is set to Enable, this
parameter is displayed on the screen. Set this
parameter to determine whether the port is
used to detect the status of the PDU bypass
input switch, or system maintenance switch.
. The Control screen is displayed.
4 LCD and WebUI
. The login screen for
121