UPS5000-A-30 kVA, 40 kVA and 80 kVA
User Manual
Alarm ID
Alarm
(Alarm
Name
ID-Cause
ID)
0032-1
Battery
overvoltage
protection
0036-2
Battery
maintenance
reminder
0037-1
Battery
undervoltage
0040-7
Rectifier
abnormal
Issue 13 (2022-01-19)
Severity
Cause
Critical
● The battery
voltage is
greater
than the
upper
threshold.
● The
configured
number of
batteries is
less than
the actual
number.
● The actual
number of
batteries
does not
meet
requirement
s.
Warning
The time for
maintenance
arrives.
Critical
● The UPS
has worked
in battery
mode for an
extended
amount of
time.
● The charger
is faulty.
Critical
● The fan for
the power
unit is not
functioning
properly.
● The air
channel for
the power
unit is
obstructed.
Copyright © Huawei Technologies Co., Ltd.
Solution
1. Check the battery voltage.
2. Check that the configured number of
batteries matches the actual number.
3. Check that the actual number of
batteries meets requirements.
Maintain the batteries.
1. Check whether the battery voltage is
normal.
2. Check whether the output is
overloaded.
3. Check whether any battery is
damaged. If yes, replace the battery.
4. Check whether any battery charger
generates an alarm. If yes, replace
the faulty unit.
1. Check that the air channel for the
unit is free from blockage.
2. Check whether the fans are
functioning properly. Replace the
power unit if the fans are faulty.
B Alarm List