Huawei UPS5000-A-30 User Manual page 52

Hide thumbs Also See for UPS5000-A-30:
Table of Contents

Advertisement

UPS5000-A-30 kVA, 40 kVA and 80 kVA
User Manual
Item
Bypass input
Bypass input current (A)
Recommended
cross-sectional area
(mm
Output
Output current (A)
Recommended
cross-sectional area
(mm
Battery input
Nominal discharge current (384 V
voltage; thirty-two 12 V batteries)
(A)
Maximum discharge current (end of
discharge current of thirty-two 12 V
batteries, namely, 1.67 V/cell
discharge current of 192 2 V cells)
(A)
Recommended
cross-sectional area
(mm
Ground cable
Recommended
cross-sectional area
(mm
Issue 13 (2022-01-19)
N
L1
L2
2
)
L3
N
U
V
2
)
W
N (Increase
the cross-
sectional area
at non-linear
load)
+
N
2
)
PE
2
)
Copyright © Huawei Technologies Co., Ltd.
30 kVA
40 kVA
46
61
4 x 10
4 x 16
46
61
4 x 10
4 x 16
82
110
98
131
3 x 16
3 x 35
1 x 10
1 x 16
3 Installation
80 kVA
122
4 x 35
122
4 x 35
219
262
3 x 95
1 x 25
42

Advertisement

Table of Contents
loading

Table of Contents