B Alarm List - Huawei UPS5000-A-30 User Manual

Hide thumbs Also See for UPS5000-A-30:
Table of Contents

Advertisement

UPS5000-A-30 kVA, 40 kVA and 80 kVA
User Manual
Alarm ID
Alarm
(Alarm
Name
ID-Cause
ID)
0001-1
Mains
voltage
abnormal
0001-2
0001-3
0004-1
Mains ph.
Reversed
Issue 13 (2022-01-19)
Severity
Cause
Minor
● Cable
connections
are
incorrect.
● The mains
is not
normal.
● The power
unit is
faulty.
● Cable
connections
are
incorrect.
● The mains
is not
normal.
● The mains
input fuse
for the
power unit
is blown.
The mains is
not normal.
Minor
Cable
connections
are incorrect.
Copyright © Huawei Technologies Co., Ltd.
B
Alarm List
Solution
1. Check whether cables to mains are
disconnected, loose, or incorrectly
connected.
2. If cable connections are correct,
measure the mains voltage with a
multimeter. If the mains voltage
exceeds 280 V, the mains input is not
normal; if the mains voltage is less
than 272 V, the sampling circuit of
the power unit is not normal.
Replace the faulty unit.
1. Check whether cables to mains are
disconnected, loose, or incorrectly
connected.
2. If cable connections are correct,
measure the mains voltage with a
multimeter. If the mains voltage is
less than 80 V, the mains voltage is
not normal; if the mains voltage
exceeds 88 V, the power unit
sampling circuit or fuse may not be
working properly. Replace the faulty
unit.
Check the mains.
Verify the cable connections.

B Alarm List

188