The Setup page allows the user to change the settings of the timers and the signals.

Figure 4-11: Setup Page

TIMER SETUP
Auto Start Delay: During the scrubber start-up, air can be found in the scrubber's piping
system. This timer protects the water monitoring system against air entering the system by
delaying sampling during the start-up phase. The On/Off valve or the pump will first be
turned ON after the Auto Start Delay.
Flow Alarm Delay: This timer allows small fluctuations of the flow without giving Flow
Alarm. When the water monitoring system is sampling, this timer controls for how long
the flow may be missing before the Flow Alarm is triggered. This timer provides dry run
protection of the pump, hence changing the timer setting should be considered carefully.
Flow Establish Time: When the On/Off valve or the pump is activated, the water
monitoring system starts sampling. This timer allows the water to travel from the On/Off
valve or the pump to the flow sensor. If the flow sensor is triggered within the Flow
Establish Time, then the water monitoring system will continue sampling. If flow sensor
is not triggered (i.e. no flow) within the set time, then the Flow Alarm will trigger, and the
system will stop sampling.
Flow Filter Time
The flow filter time controls the dampening effect of the flow signal. If the flow value is
fluctuating, the setting of flow filter time must be increased.
The factory settings of these parameters can be found in the test and configuration sheet
attached to each system.

Figure 4-12: Timer Setup Page

Ver.5.0 – Revision March 2022
Page 23 of 110