Omron H3CR-A Manual page 85

Hide thumbs Also See for H3CR-A:
Table of Contents

Advertisement

H3DR-A/P/M
PNP Input Models
The inputs of the H3DR-AP/--ASP/-PP are voltage (voltage imposition or open) inputs.
H3DR-AP/-ASP
Voltage Inputs
No-contact Input
(Connection to PNP output sensor.)
12 to 24 VDC (sensor
power supply)
+
DC power
--
supply
Timer
Sensor
A
1
Start/reset/
gate
A
2
Operates with transistor ON
H3DR-PP
Voltage inputs
No-contact Input (for 24 VDC/VAC Model)
(Connection to PNP output sensor.)
Sensor
A
B
1
Start
24 VDC
A
2
Operates with transistor ON
Voltage Input Signal Levels
1. Transistor ON
Residual voltage: 1 V max.
(Voltage between terminals B
No-contact
input
the operating voltage range.)
2. Transistor OFF
Leakage current: 0.01 mA max.
(Voltage between terminals B
the operating voltage range.)
Use contacts that can adequately switch 0.1 mA at each
Contact
voltage to be imposed. (When the contacts are ON or
input
OFF, voltage between terminals B
than the operating voltage range or less than the
operating voltage range respectively.)
Contact Input
Timer
(0 V)
Operates with relay ON
Contact Input
Timer
1
Operates with relay ON
and A
must be more than
1
2
and A
must be less than
1
2
and A
1
2
Voltage Input Signal Levels
No-contact
input
A
1
Start/reset/
gate
Contact
input
Timer
A
B
1
1
Start
A
2
must be more
H3DR-A/P/M
1. Voltage imposition
Transistor ON
Residual voltage: 1 V max.
Impedance when ON: 1 k$ max.
2. Open level
Transistor OFF
Impedance when OFF: 100 k$ min.
Use contacts which can
adequately switch 0.1 mA at 5 V
85