H3DR-H
Time Ranges
Time ranges
S-series
L-series
Note: If the above minimum power ON time is not secured, the H3DR may not operate. Be sure to secure the above minimum power ON time.
Allow at least 3 s for repeat synchronization of time-out operations (see Precautions on page 107).
Ratings
Rated supply voltage (see note)
Operating voltage range
Power consumption
Control outputs
Note: A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
Characteristics
Accuracy of operating time
Setting error
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Impulse withstand voltage
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
EMC
Enclosure ratings
Weight
Setting
Time scale: x 0.1
Time scale: x 1
Time scale: x 1
Time scale: x 10
100/110/120 VAC (50/60 Hz), 200/220/240 VAC (50/60 Hz), 24 VAC/DC (50/60 Hz),
48 VAC/DC (50/60 Hz)
85% to 110% of rated supply voltage
100/110/120 VAC: approx. 0.5 VA
200/220/240 VAC: approx. 0.8 VA
24 VAC/DC:
approx. 0.17 VA (AC), 0.13 W (DC)
48 VAC/DC:
approx. 0.36 VA (AC), 0.34 W (DC)
Contact output: 5 A at 250 VAC, resistive load (cos% = 1)
!1% FS max. (1% FS !10 ms max. in ranges of 1.2 s)
!10% FS !0.05 s max.
!0.5% FS max. (!0.5% FS !10 ms in ranges of 1.2 s)
!2% FS max. (!2% FS !10 ms in ranges of 1.2 s)
100 M$ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed
non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
3 kV (between power terminals) for 100 to 120 VAC, 200 to 240 VAC
1 kV for 24 VAC/DC, 48 VAC/DC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
for 100 to 120 VAC, 200 to 240 VAC
1.5 kV for 24 VAC/DC, 48 VAC/DC
!1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width:
100 ns/1 &s, 1-ns rise)
Malfunction:4 kV
Destruction: 8 kV
Destruction:10 to 55 Hz with 0.75-mm single amplitude each in three directions
Malfunction:10 to 55 Hz with 0.5-mm single amplitude each in three directions
Destruction: 980 m/s
2
Malfunction:98 m/s
Operating:--10"C to 55"C (with no icing)
Storage: --25"C to 65"C (with no icing)
Operating: 35% to 85%
Mechanical:10 million operations min. (under no load at 1,200 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h)
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity RF-interference: ENV50140: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Conducted Disturbance:
Immunity Burst:
IEC: IP40
Approx. 135 g
Setting range
0.1 to 1.2 s
1 to 12 s
1 to 12 s
10 to 120 s
2
(100G) each in three directions
(10G) each in three directions
EN55011 Group 1 class A
EN55011 Group 1 class A
IEC801-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
ENV50141: 10 V (0.15 to 80 MHz) (level 3)
IEC801-4:
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
H3DR-H
Min. power ON time
0.1 s min.
0.3 s min.