H3CR-F
Ratings
Rated supply voltage (see note)
Operating voltage range
Power reset
Power consumption
Control outputs
Note: A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
Characteristics
Accuracy of operating time
Setting error
Reset time
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Impulse withstand voltage
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
Case color
Enclosure ratings
Weight
Engineering Data
10,000
5,000
1,000
30 VDC L/R = 7 ms
500
100
250 VAC (cos% = 0.4)
Load current (A)
100 to 240 VAC (50/60 Hz),12 VDC, 24 VAC/DC (50/60 Hz), 48 to 125 VDC
85% to 110% of rated supply voltage; 90% to 110% with 12-VDC models
Minimum power-opening time: 0.1 s
100 to 240 VAC: approx. 10 VA; 12 VDC: approx. 1 W;
24 VAC/DC: approx. 2 VA (AC), approx. 1 W (DC); 48 to 125 VDC: approx. 1.5 W
Contact output: 5 A at 250 VAC, resistive load (cos% = 1)
!0.3% FS max. (!0.3% FS !10 ms in ranges of 1.2 and 3 s)
!5% FS !0.05 s max.
0.1 s max.
!0.5% FS max. (!0.5% FS !10 ms in ranges of 1.2 and 3 s)
!2% FS max. (!2% FS !10 ms in ranges of 1.2 and 3s)
100 M$ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed
non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
3 kV (between power terminals) for 100 to 240 VAC, 48 to 125 VDC
1 kV for 12 VDC, 24 VAC/DC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
for 100 to 240 VAC, 48 to 125 VDC
1.5 kV for 12 VDC, 24 VAC/DC
!1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width:
100 ns/1 &s, 1-ns rise)
!400 V for 12 VDC
Malfunction:8 kV
Destruction: 15 kV
Destruction:10 to 55 Hz with 0.75-mm single amplitude each in three directions
Malfunction:10 to 55 Hz with 0.5-mm single amplitude each in three directions
Destruction: 980 m/s
2
Malfunction:98 m/s
Operating:--10"C to 55"C (with no icing)
Storage: --25"C to 65"C (with no icing)
Operating: 35% to 85%
Mechanical:20 million operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)
Light Gray (Munsell 5Y7/1)
IEC: IP40
Approx. 100 g
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cos% = 1)
250 VAC/30 VDC
(cos% = 1)
2
(100G) each in three directions
(10G) each in three directions
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In
both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
H3CR-F
39