H2F
Three pairs pairs of setting tabs are attached.
Store the spare tabs in the compartment at the lower right corner of
the front panel.
Manual Switch
SPST-NO Output
A 3-position selector switch, located at the lower left corner of the
front panel, determines output operation. In the OFF position, the
control output is forcibly turned OFF regardless of the setting of the
programming tabs. Set to the AUTO position, the output is turned
ON and OFF according to the settings of the programing tabs. In the
ON position, the output is forcibly turned ON regardless of the set-
ting of the programming tabs.
SPDT Output
When the manual switch at the lower left corner of the front is set to
the OFF position, both load 1 (connected across terminals 4 and 5)
and load 2 (across 5 and 6) are turned OFF.
When it is set to the AUTO position, the output is turned ON and OFF
according to the setting of the programming tabs.
When the manual switch is set to the ON position, load 1 (connected
across terminals 4 and 5) is turned ON and load 2 (across 5 and 6) is
turned OFF.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. L13-E1-3
Output Indicator
The output indicator at the upper left corner of the front panel shows
the status of the output when the manual switch is set to the AUTO
position.
In addition, the output can be manually turned ON or OFF by rotat-
ing the knob clockwise (in the arrow direction). The knob will not turn
counterclockwise.
Note on H2F-D, -DF series (synchronous motor versions)
Before using the timer, select the appropriate frequency of your area
by the frequency selector switch provided on the upper part of the
rear panel.
Upper part of rear panel
(cycles per second)
H2F
269