Differences In Available Functions Depending On The Cpu Unit (Nj Or Cj Series; A-1-1 Functional Differences; A-1-2 Differences In Accessing Data From User Program - Omron CJ Series Operation Manual

Machine automation controller
Hide thumbs Also See for CJ Series:
Table of Contents

Advertisement

Appendices
A-1
Differences in Available Functions
Depending on the CPU Unit (NJ or
CJ Series)
Some of the specifications when a CompoNet Master Unit is connected to a CJ-series CPU Unit are dif-
ferent from the specifications when the CompoNet Master Unit is connected to an NJ-series CPU Unit.
A list of these differences is provided below.
A-1-1
Functional Differences
There are differences in function support, function names, and specifications between when a Com-
poNet Master Unit is connected to a CJ-series CPU Unit and when the CompoNet Master Unit is
connected to an NJ-series CPU Unit.
Functions with Different Names
The names of the following functions are different between when a CompoNet Master Unit is connected
to a CJ-series CPU Unit and when the CompoNet Master Unit is connected to an NJ-series CPU Unit.
The corresponding names are listed in the following table.
Item
Backup functions
*1 An NJ-series CPU Unit with unit version 1.03 or later and Sysmac Studio version 1.04 or higher are required.
A-1-2
Differences in Accessing Data from User Program
When the CompoNet Master Unit is used with an NJ-series CPU Unit, the device variables for the CJ-
series Unit are used as the basic means to access the CompoNet Master Unit from the user program.
The following tables give the I/O memory addresses in a CJ-series CPU Unit and the corresponding
device variables for CJ-series Units in the NJ-series CPU Unit. (The I/O memory of the CJ-series CPU
Unit is the same as the memory used for CJ-series Units.)
Words Allocated to Special I/O Units in CIO Area
n (first word) = CIO 2000 + (10 × Unit number)
MACH
N
No.
1
X10
0
X10
A-2
CompoNet Master Unit connected
to a CJ-series CPU Unit
Simple backup function
Backup with PLC backup tool
The words that are allocated to the
CompoNet Master Unit in the CIO and
DM Areas depend on the unit number
that is set on the unit number switches
on the front panel of the Unit.
CJ-series CompoNet Master Unit Operation Manual for NJ-series CPU Unit (Cat. No. W493)
CompoNet Master Unit connected to an NJ-
series CPU Unit
SD Memory Card backup function
Sysmac Studio Controller backup function
*1