rate other than 93.75 kbps, and 30 s for 93.75 kbps.
the front of the Master Unit will flash red and the seven-segment display will show d5. How-
ever, if the applicable Slave Unit subsequently starts participating, *_RegTblErr (Registration
Table Verification Error Flag) will change to FALSE and the error display will be cleared.
*1 The Registered Slave Unit Participation Monitoring Time is disabled when the Registered Slave Unit Participa-
tion Standby Mode is enabled.
Note Remote I/O communications will not operate if SW4 (REGS) is set to ON on the Master Unit when the power
supply is turned ON and the Registration Table data is not valid. The MS indicator on the front of the Master
Unit will flash red, and the seven-segment display will show E8.
Creating Registration Tables
Registration Tables are created either by automatic generation from the CX-Integrator or by editing
and transferring them.
Personal computer
(CX-Integrator)
Method 2: Editing and Downloading a Registration Table
Method 1: Automatic Registration Table Generation
CJ-series CompoNet Master Unit Operation Manual for NJ-series CPU Unit (Cat. No. W493)
NJ-series CPU Unit
Edited Registration Table
Node Model
0
ID16
1
OD16
:
:
Downloaded
(along with other Master
Unit parameters)
5 Remote I/O Communications
*1
) At the same time, the NS indicator on
Registration Table editing
CompoNet Master Unit
Registration with correct
correspondence between
node addresses and models
CompoNet Network
Word Slaves
Bit Slaves
5-17
5