When this parameter is saved on the reader, a plausibility test is run. If an error occurs, the reader replies
with STATUS = {0x11}.
Changes to TRANS-FORM take effect only after writing/saving the configuration block CFG2 in the
EEPROM and resetting the reader.
8 data bits and a stop bit always need to be used.
TR-
With this byte, you can specify the maximum response time for transponder commands.
RESPON
TR-RESPONSE-TIME begins when the reader has received a new command. The reader sends a response
SE-TIME
protocol at the latest when the TR-RESPONSE-TIME elapses. In this case, the current commands between
the reader and transponder are aborted. If this time is too short, the interface status "0x83 RF communications
error" appears.
The response time is calculated as follows: TR-RESPONSE-TIME * 100 ms. The range of values of TR-
RESPONSE-TIME is between 1 and 65535.
Notes:
"TR-RESPONSE-TIME" has no effect on the protocols for the configuration of the reader and the protocols
for controlling the reader.
"TR-RESPONSE-TIME" must be lower than "Block Timeout" in the settings of the COM port of the host.
SCAN-
Selection of the communications port for "Scan Mode".
INTER-
Bit
FACE
Function
Function
IF-NO
INTER-
Flag for activating the communications port
FACE
Bit
Function
Function
RS232
READER-
The mode of the reader can be defined with this byte.
MODE
Bit
Function
Function
SCAN-E
RF290R
Configuration Manual, 09/2014, C79000-G8976-C377-01
7
6
-
-
Description
Interface number
b000 RS-232 (default)
b01x reserved
b1xx reserved
7
6
-
-
Description
b0 activate
b1 deactivate
7
6
BRM-E
-
Description
By setting this bit, the "Scan Mode" can be activated.
b0 Host mode
b1 Scan mode
5
4
3
-
-
-
5
4
3
-
-
-
5
4
3
-
-
-
Configuration parameters (CFG)
5.2 CFG1: COM interface
2
1
IF-NO
2
1
-
-
2
1
-
-
0
0
RS232
0
SCAN-E
25