Configuration parameters (CFG)
5.2 CFG1: COM interface
Name
Description
COM-
Bus address of the reader (0 .. 254) for communication via the asynchronous interface.
ADR
Notes:
When this parameter is saved on the reader, a plausibility test is run. If an error occurs, the reader replies
with STATUS = {0x11}.
The address 255 must not be configured.
The reader can be addressed at any time using the COM address 255 in the transmit protocol. It then
replies with the set address.
BAUD
Here you set the baud rate of the asynchronous interface.
BAUD
0x05
0x06
0x07
0x08
0x09
0x0A
Notes:
When this parameter is saved on the reader, a plausibility test is run. If an error occurs, the reader replies
with STATUS = {0x11}.
A change to the baud rate only takes effect after writing/saving the configuration block CFG1 in the
EEPROM and resetting the reader.
If the user sets an invalid baud rate, the reader sets the baud rate to 38,400 Bd.
TRANS-
With this byte, you define various parameters of the data transfer format of the asynchronous interface.
FORM
Bit
Function
Function
P
D
S
24
Baud rate
4800 Baud
9600 Baud
19200 Baud
38400 Baud
57600 Baud
115200 Baud
7
6
0
0
Description
Type of parity
b00 none
b01 even (default)
b10 odd
b11 reserved
Number of data bits
b0 1 bit
b1 reserved
Number of stop bits
b0 8 bits
b1 reserved
5
4
3
0
0
S
Configuration Manual, 09/2014, C79000-G8976-C377-01
2
1
0
D
P
RF290R