st
Mode
1
code
11(21)
3
6
7
8
9
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
Description function
Fan setting of heating
Sensitivity presence sensor
Airflow adjustment
Compensation by floor sensor
Compensation of floor
temperature
nd
2
code
Description selection
01
Standard
02
Slight increase
03
Increase
01
High sensitive
02
Low sensitive
03
Standard
04
Disable presence sensor
01
Manual setting (see mode 23-6
below)
02
ESP auto judgment completed
03
Start ESP auto judgment (if
control set to fan only + ON)
01
Floor sensor disabled
02
Air suction temperature priority
03
Standard
04
Floor temperature priority
01
-4°C
02
-2°C
03
No correction
04
+2°C
6
Technical data
|
Service manual
467
Need help?
Do you have a question about the VRV IV+ and is the answer not in the manual?
Questions and answers