Daikin VRV IV+ Service Manual page 450

Advertisement

6
|
Technical data
Wiring
Component
symbol
R15T
Compressor body
thermistor
R21T,
Discharge pipe
R22T
thermistor
R15T
Compressor body
thermistor
A3P,
Radiation fin
A6P,
temperature
A4P,
A7P
Service manual
450
Description
Trigger
Overheat
Temperature >135˚C for 3 times
protection
within 100 minutes
Reset: Temperature <100˚C
Overheat
Temperature >120˚C for 2 times
protection
within 10 minutes
Reset: Temperature <100˚C
Overheat
Temperature >120˚C for 2 times
protection
within 10 minutes
Reset: Temperature <100˚C
Overheat
Temperature >110˚C
protection
Reset: Temperature <107˚C
Temperature >114˚C
Drop control is visible through service checker tool.
Retries are monitored by field setting Mode 1 (monitor mode): 1-23/24/25. See
4
"6.9 Field
settings" [
 455].
Forced stops will trigger error codes. Active errors are visible on the outdoor unit
7-Segment LED Display, remote controller displays and central controller devices.
To consult the error history, see "To check the error history" in
4
"2 Troubleshooting" [
 14].
Error
Action type
F3
Forced stop
F3
Forced stop
F3
Forced stop
Drop control
L4
Forced stop
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05