6
|
Technical data
(
)
*
51
Multi outdoor main/sub setting
52
Drainpan heater output signal
70
Capacity‑less heating
81
Cooling comfort setting
82
Heating comfort setting
83
Cool/heat master allocation in case
VRV + RA installed together
84
BP initial EV opening in heating
mode
85
Timer - refrigerant leak detection
function operation (days)
86
Timer - refrigerant leak detection
function performed setting
Service manual
464
Item
Display
2.51
0
Auto
1
Forced master
2
Forced sub 1
3
Forced sub 2
2.52
0
Off
1
Compressor operation output at X17A
2
Drainpan heater function activated, output
at X10A
3
Drainpan heater function activated, output
at X10A
2.70
0
Off
1
Operation off
2
Thermo off
3
Operation off + thermo off
2.81
0
Eco
1
Mild
2
Quick
3
Powerful
2.82
0
Eco
1
Mild
2
Quick
3
Powerful
2.83
0
VRV
1
RA
2.84
0
400 pls
1
500 pls
2
600 pls
3
300 pls
2.85
0
365
1
180
2
90
3
60
4
30
5
7
6
1
2.86
0
Off
1
Single
2
Permanent
(
)
Content
**
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05