Daikin VRV IV+ Service Manual page 466

Advertisement

6
|
Technical data
6.9.6 Overview of field settings for indoor units
The overview lists all possible settings for the indoor units. The availability of the setting depends on the indoor
unit type, see "Field settings as per type indoor unit". Bold content is default setting.
st
Mode
1
code
10(20)
0
1
2
3
4
5
6
7
8
9
Service manual
466
Description function
Filter contamination heavy / light
Long life filter type
Air thermistor selection
Display filter sign
Spare
Remote controller thermistor
visible by central control device in
group wiring P1P2
Air thermistor selection in group
wiring P1P2
Absence delay detecting time
(presence sensor)
Compensation air sensor heating
Spare
nd
2
code
Description selection
01
Filter contamination: light LL
2500 hr / flat 200 hr
02
Filter contamination: heavy LL
1250 hr / flat 100 hr
01
Long life filter
02
Super long life filter
04
Oil guard filter
01
Combined control
02
Only the return air thermistor
03
Only the remote controller
thermistor
01
Display
02
No display
--
--
01
No
02
Yes
01
Return air thermistor (individual
units)
02
Thermistor designated by field
set 20-2 (see above)
01
30 minutes
02
60 minutes
01
Add 2.0°C to measurement air
sensor
02
Measurement air sensor
--
--
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05