1-8
Chapter 1: Module Overview
Blink
Name and Description
Code
Offline
Rapid continuous blinking indicates the
rapid
module is offline and outputs are
disabled.
Run Mode
ON
The LED is solid green.
Major Fault or Power-up or Power Off
The module is just powering up and not
initialized yet or there is a major
OFF
hardware fault causing the module to be
held in reset by the controller. LED
control is not possible for this condition
and will remain off.
Calibration invalid or corrupted
This code will be seen for newly
3
manufactured boards that have yet to be
calibrated.
Serial Number Invalid or Corrupted
This code will only be seen if the
4
module has been calibrated but the serial
number is not programmed, or the flash
memory sector is corrupted.
Analog Communications Error – Input
A communications error or connection
5
error took place between the MCU and
ADC or PGA circuitry.
Section 1.5
System
Overview
User's Manual Pub. 0300306-02 Rev. B
Table 1-5 LED Blink Codes Table For Firmware 2.1
The 2085sc-IF16 module is expected to operate indefinitely. It does not require
periodic maintenance or calibration. The module communicates to the controller
through the bus interface. The module also receives 5 VDC and 24 VDC through
the bus interface.
Resolution
Set controller to RUN mode.
This will also be seen during power-on while it is
initializing.
Module is initialized with no hardware fault
detected. Module is in Run mode.
Give plenty of time for power-on.
Power-cycle to try and clear the error condition. If
unsuccessful, the module must be replaced.
Factory calibration must be performed.
Return the module to Spectrum Controls, Inc. for
recalibration.
Serial number must be programmed.
Return the module to Spectrum Controls, Inc. for
recalibration.
Power-cycle to try and clear the error condition. If
unsuccessful, the module must be replaced.