Pepperl+Fuchs FieldConnex HD2-DM-A Manual page 95

Advanced diagnostic solutions
Hide thumbs Also See for FieldConnex HD2-DM-A:
Table of Contents

Advertisement

H D 2 - D M - A / D M - A M
Requirements
Cables,
Power Hub,
HD2-DM-A,
supply power and
Host
are connected to the segment.
Possible Measurements/Checkouts
all measurements described in section above.
Background mode:
Signal level on the bus (missing Terminator)
Noise level on the bus
Jitter on the bus
Host signal polarity
UI-mode:
number of transmitted telegrams
number of Cyclic Redundancy Check faults (CRC)
number of Pass Token Misses
Oscilloscope monitoring of the bus signal
Oscilloscope triggering of CRC or framing faults
If the Segment Focus is enabled for one segment, only the checks/mea-
surements described at point 2 for the other three segments are possi-
ble.
If the Oscilloscope monitor is enabled, parallel to them only the checks/
measurements described at point 2 are possible.
Oscilloscope monitors exclude each other. Only one can run at a time.
Host/Slave checkout
Requirements
Cables,
Power Hub,
HD2-DM-A,
Supply power,
Host and
Slaves
are connected to the segment.
Possible Measurements/Checkouts
all measurements described before.
Background mode:
Signal level of each slave on cyclic data exchange
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Use Cases and Troubleshooting
Copyright Pepperl+Fuchs, Printed in Germany
95