H D 2 - D M - A / D M - A M
LED indication Fault type
PRI PWR and/or
Supply power failure:
SEC PWR LEDs
possible reasons:
are off
One segment
A segment/field de-
LED is flashing
vice maintenance re-
yellow (on/off
quired alarm is active.
with 2 Hz)
All segment
A system mainte-
LED are flashing
nance required alarm
yellow (on/off
is active.
with 2 Hz)
One segment
Any segment/field de-
LED is flashing
vice alarm is active.
red (on/off with
2 Hz)
All segment
Any system alarm is
LEDs are flash-
active
ing red
(on/off with 2
Hz)
Any (or all) seg-
A hardware fault in-
ment LEDs
side HD2-DM-A is de-
lights solid red
tected
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
• no primary and/or
secondary sup-
ply power is avail-
able
• supply power is
less than 19.2 V
• supply power is
higher than 35 V
(32 V if at least
one non-isolated
power module is
plugged-in or
configured)
Product Specifications HD2-DM-A
Remedy
Connect diagnostic PC and carry out
a complete system diagnosis:
Bulk power supply switched on and
healthy?
Verify that the wiring is secure:
• Tug on the wires/cable-clamps
• Measure the DC voltage at the ter-
minal block connector to the bulk
power supply
Connect diagnostic PC and carry out
a complete system diagnosis:
• DC unbalance
• too high jitter level
• too high noise level
Bus segment...
• ...badly terminated?
• ...miswired (shield connections)?
• ...short circuit overload?
Power supply/conditioner modules
healthy and well mounted?
Connect diagnostic PC and carry out
a complete system diagnosis:
Bulk power supply voltage correct?
Board type configuration correct?
Board redundancy configuration cor-
rect?
Replace the device with a new one!