Operation with the Diagnostic Manager
Perform System Commissioning
1. Open the Commissioning Wizard
2. Press the button System Commissioning
Current motherboard and supply data is shown
3. Press the button Next
Snapshot recording occurs and current system data with automati-
cally calculated maintenance and alarm limits are shown
If necessary modify the limit values, before storing them to the Diagnostic
Module.
The out of specification alarm for the primary and secondary power sup-
ply will be enabled automatically by default.
4. Press button Next
System warning and alarm limit values are now stored to the Diag-
nostic Module
Figure 8.2: System commissioning successful
Perform Segment Commissioning
1. Open the Commissioning Wizard
2. Perform System commissioning (see above)
3. Press the button Segment Commissioning
Connected field devices are shown
4. Press the button Next
Current segment and field device data is shown
If you are using a National Instruments Card (NI-Card), current Device
tags can be take over by pressing the Read Tags button.
5. Press the button Next
Snapshot recording occurs and a printable report is generated and
stored within the Snapshot Explorer (see chapter 8.4)
6.
Press the button Next
Current system data with automatically calculated limits are shown
Subject to reasonable modifications due to technical advances.