-25mA
2.1.4
Using an analogue output as a transducer
You can use an analogue output as a transducer to transmit the controller's set point, AC measurements or power
management information to an external system.
You can select the output range for the transducer. That is, 0-20mA, 4-20mA, 0-10V, or -10-0-10V.
You can also select the output range for the value. For example, for the genset apparent power (menu 5850), select the
minimum in 5855, and select the maximum in 5844.
Parameters for using an analogue output as a transducer
Menu Value
5690 P ref
5700
Q ref
5710
cos phi ref
5820 P1*
5830 P2*
5840 P3*
5850 S
5860 Q
5870
cos phi
5880 f
5890 U
Options E F AGC-4 Mk II 4189341277C EN
Controller offset
100%
0%
Details
The controller's power set point.
For example, for MWM TEM controllers.
The controller's reactive power set point
The controller's cos phi set point
Genset active power
Genset active power
Genset active power
Genset apparent power
Genset reactive power
cos phi of the power from the genset
Genset frequency
Genset L1-L2 voltage
25mA