Inverter Applications; Resistive Loads; Motor Loads - Xantrex Freedom XC2000-230V Owner's Manual

Inverter/charger
Table of Contents

Advertisement

Inverter Applications

Inverter Applications
The Freedom XC performs differently depending on the AC loads
connected to it. If you are having problems with any of your loads,
read this section.

Resistive Loads

These are the loads that the inverter/charger finds the simplest
and most efficient to drive. Voltage and current are in phase (that
is, in step with one another). Resistive loads usually generate
heat in order to accomplish their tasks. Toasters, coffee pots, and
incandescent lights are typical resistive loads. It is usually
impractical to run larger resistive loads—such as electric stoves
and water heaters—from an inverter due to their high current
requirements. Even though the inverter/charger can most likely
accommodate the load, the size of battery bank required would be
impractical if the load is to be run for long periods.
82

Motor Loads

Induction motors (that is, motors without brushes) require two to
six times their running current on start up. The most demanding
are those that start under load, for example, compressors and
pumps. Of the capacitor start motors (typical in drill presses, band
saws, etc.), the largest you can expect to run is ½ hp (the transfer
relays are rated at 2 hp). Universal motors are generally easier to
start. Since motor characteristics vary, only testing will determine
whether a specific load can be started and how long it can be run.
If a motor fails to start within a few seconds or loses power after
running for a time, it should be turned off. When the
inverter/charger attempts to start a load that is greater than it can
handle, it will turn itself off after a few seconds.
Long Transfer Times
The Freedom XC may take a long time (~ 0.1–0.2 s) to transfer to
Battery Mode when shore power is cut off while powering a motor
load. Motor loads typically "freewheel" when power is removed (for
example, a grinder) and causes a longer transfer time. The longer
transition from shore power to inverter power may cause
connected computers or other sensitive equipment to operate
incorrectly. To avoid this effect, do not connect motor loads
together with sensitive equipment to the inverter/charger for
power.
Freedom XC 2000 - 230V Owner's Guide