Overload Conditions; High Surge Loads - Xantrex Freedom XC2000-230V Owner's Manual

Inverter/charger
Table of Contents

Advertisement

Operating
Battery
Condition
Voltage
High
Voltage
17.0 V
Shutdown
975-0821-01-01
Comment
The display shows error code
E02 alternating with the battery
voltage. The red status LED
turns on. 
NOTE: Although the Freedom
XC incorporates over-voltage
protection, it can still be
damaged if input voltage
exceeds 18.0 VZ.

Overload Conditions

There are two kinds of overload conditions – an overload warning
and an overload shutdown.
Overload
When the Freedom XC's AC load is approximately 100 W
Warning
below the overload shutdown limit of rated watts, the
audible alarm beeps once and the LCD screen shows a
warning code E06.
Overload
When the Freedom XC's AC load increases to near
Shutdown
~2100 W, the audible alarm beeps every 5 s for 1 min
and the LCD screen shows a error code E03. The Status
LED turns solid RED.

High Surge Loads

Some induction motors used in freezers, pumps, and other motor-
operated equipment require high surge currents to start. The
Freedom XC may not be able to start some of these motors even
though their rated steady state current draw is within the
inverter/charger's limits. The unit will shut down and indicate an
overload shutdown.
Operating Limits
69