Table 13 Error codes displayed on the LCD screen
Error Code
Condition
Low battery voltage
shutdown is imminent
depending on the setting,
E01
see Maintaining the
Freedom XC Unit on page
72.
High battery voltage
E02
shutdown
> 17.0 VZ
AC output overload
E03
shutdown
E04
Over-temperature shutdown
E06
AC output overload warning
76
Mode
Check battery status and recharge if necessary.
Battery mode
Check for proper DC cable sizing.
(inverting)
Check for loose connections and tighten if necessary.
Battery mode
Check for external charging sources, such as a PV charger and
(inverting)
an over voltage alternator. Disconnect, if necessary.
Reduce the loads connected to the AC outlet of the unit.
Battery mode
Check appliances that have high-surge ratings and disconnect
(inverting)
if necessary.
Reduce the loads connected to the AC outlet of the unit.
Battery mode
Check that the ventilation grille is not blocked.
(inverting)
Check for ambient temperature and move the unit to a cooler
location whenever possible.
Battery mode
Reduce the loads connected to the AC outlet of the unit.
(inverting)
Action