Status Indicator; B426; General; Address Setting - Bosch AMAX 2100 Installation Manual

Amax panel
Hide thumbs Also See for AMAX 2100:
Table of Contents

Advertisement

AMAX panel
AMAX 2100 / 3000
AMAX 3000 BE / 4000
Figure 4.6: Connecting DX3010 to the AMAX Panel
4.4.4

Status Indicator

None.
4.5

B426

4.5.1

General

AMAX panel supports up to two communication modules:
The B426 Ethernet communication module supports monitored two-way IP communication via
Ethernet to perform alarm transmission, remote programming, and control of the AMAX panel.
Installation
1.
2.
3.
4.5.2

Address Setting

Set the rotary switch to 6 which corresponds to option bus address 134 for the first B426.
Set the rotary switch to 9 which corresponds to option bus address 250 for the second B426.
4.5.3

Wiring

The following graphic shows how to wire B426 to the option bus 1 or 2 of the AMAX panel.
Make sure, that the cable doesn't exceed 150 meters.
Bosch Sicherheitssysteme GmbH
ITS-DX4020-G and B426 or
B426 and B426
Disconnect all power supplies of the AMAX panel before installing B426.
Use the standard three-hole installation mode to install B426 in the enclosure of the
AMAX panel or another enclosure. For more information refer to Module Installation, page
26 and to B426 Ethernet Communication Module.
Use network or direct connection to access the built-in web server when reconfiguring
the module or when connecting the module to the AMAX panel with RPS.
Optional Modules and Peripheral Devices | en
DX3010
Installation Manual
DX3010
_
+
12V
2015.05 | 06 | F.01U.309.277
19