AMAX panel
2.
P
Condition:
1.
2.
Restore:
1.
2.
Supervise:
1.
2.
3.
P
Condition:
The Aux power supply voltage is lower than 9V.
Restore:
4
Supervise:
1.
2.
3.
P
Condition:
Bosch option bus power supply voltage is lower than 9V+-5%.
Restore:
4
Supervise:
1.
2.
3.
P
Condition:
Bosch Sicherheitssysteme GmbH
When the AC supply is reconnected, the MAINS indicator lights up (except in
programming mode or in code functions mode).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
Battery Low Battery
The battery voltage is lower than 11V+-1%.
No battery is connected.
Connect a battery. For more information, refer to Battery Installation, page 27.
Raise battery voltage to 12V+-1%, perform a dynamic battery test (time set in
programming address 204) and reset the fault.
Set the system to perform a dynamic battery test on a regular basis (time set in
programming address 204) and every time the system is armed or reset.
Report the low battery to the configured destination programmed on address 124.
Slow flash FAULT indicator (refer to Keypad Indicators, page 8 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
Panel Aux Power 1-2 Failure
Raise the voltage to 12V and reset the fault.
Monitor the voltage by MPU.
Report the AUX power fault to the configured destination programmed on address 124.
Slow flash FAULT indicator (refer to Keypad Indicators, page 8 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
Bosch Option Bus Power 1-2 Failure
Raise the voltage to 12V and reset the fault. For more information refer to Bosch Option
Bus, page 13.
Monitor the voltage by MPU.
Report the Bosch Option Bus Power Supply fault to the configured destination
programmed on address 124.
Slow flash FAULT indicator (refer to Keypad Indicators, page 8 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
RF Repeater 1-8 AC Power Failure
Installation Manual
Troubleshooting | en
151
2015.05 | 06 | F.01U.309.277