Bosch AVIOTEC IP starlight 8000 Operation Manual

Video fire indication systems are video content analysis systems.
Hide thumbs Also See for AVIOTEC IP starlight 8000:

Advertisement

AVIOTEC IP starlight 8000
FCS-8000-VFD-B
en
Operation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Bosch AVIOTEC IP starlight 8000

  • Page 1 AVIOTEC IP starlight 8000 FCS-8000-VFD-B Operation Manual...
  • Page 3: Table Of Contents

    AVIOTEC IP starlight 8000 Table of Contents | en Table of contents Safety instructions General Safety Messages / Notices Introduction Disclaimer About this manual Conventions in this manual Definition of optical terms 2.4.1 Illumination 2.4.2 Focal length 2.4.3 Monitoring Area...
  • Page 4: En | Table Of Contents

    | Table of Contents AVIOTEC IP starlight 8000 Troubleshooting Smoke and flame detection Camera Maintenance 10.1 Cleaning 10.2 Repair 10.3 Reset Technical data Appendices 12.1 Maximum detection distances for margin areas 12.1.1 Flame detection 12.1.2 Smoke detection Index 2016.02 | 1.0 | F.01U.318.200...
  • Page 5: Safety Instructions

    AVIOTEC IP starlight 8000 Safety instructions | en Safety instructions In this document, the following symbols and notations are used to draw attention to special situations: Danger! Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
  • Page 6 | Safety instructions AVIOTEC IP starlight 8000 Notice! No detection of moving fire. Moving fires will not be detected by the video-based fire detection. Notice! Indoor use only. This product is designed for indoor use only. Outdoor use is not allowed.
  • Page 7 AVIOTEC IP starlight 8000 Safety instructions | en Notice! Reduced detection distances at image margin area. Due to optical distorsion of the lens, the maximum detection distances at the image margin area are reduced. Notice! Avoid image regions with continuous upward motion.
  • Page 8: Introduction

    For more information please contact the nearest Bosch Security Systems location or visit www.boschsecurity.com All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
  • Page 9: Focal Length

    AVIOTEC IP starlight 8000 Introduction | en Sales room Office space In general a well illuminated monitoring area is advantageous for the video-based fire detection. Backlight should be avoided. 2.4.2 Focal length The focal length of an optical system defines the distance between a light refracting lense and the focal point.
  • Page 10: Monitoring Area

    | Introduction AVIOTEC IP starlight 8000 2.4.3 Monitoring Area The monitoring area defines the effective space that can be observed by the video-based fire detection. It is depending on the setting of the camera lens. See also – Planning, page 16 2016.02 | 1.0 | F.01U.318.200...
  • Page 11: System Overview

    The video-based fire detection is the system of choice when reliable video motion and fire detection is needed, e.g. applications which are not subjected to construction product regulation or a supplementation to existing fire detection systems. AVIOTEC IP starlight 8000 operates as stand-alone unit and doesn’t need a separate evaluation unit. Furthermore it contains all features of the Intelligent Video Analysis (IVA) which allows analyzing and evaluating moving objects in parallel.
  • Page 12: Uninterruptible Power Supply

    Algorithm The intelligent smoke and flame algorithm from Bosch analyzes video frames by means of characteristic and predefined patterns and variables. The fast detection algorithm is based on a real-time image processing on the camera firmware.
  • Page 13: Flame Detection Characteristics

    AVIOTEC IP starlight 8000 System Overview | en There are factors that can influence this kind of visual fire detection. It is important to avoid obstructions in the field of view. Sometimes obstructions cannot be prevented, e.g. building construction factors or huge machine parts. In this case it is necessary to analyze whether there is any need for further video-based fire detection cameras.
  • Page 14: Smoke Detection Characteristics

    | System Overview AVIOTEC IP starlight 8000 3.2.2 Smoke detection characteristics The algorithm analyzes smoke based on physical characteristics. Typically a plume of smoke is formed in a regular upward motion of smoke at the same position. This is characterized by a thick column of smoke.
  • Page 15: Iva

    IP network. It provides the best VMS to go with Bosch CCTV devices, leveraging the unique capabilities of Bosch cameras and recording solutions. It nevertheless offers interfaces and standards to integrate AVIOTEC IP starlight 8000.
  • Page 16: Planning

    | Planning AVIOTEC IP starlight 8000 Planning A fire safety analysis should be performed to determine the characteristics of the area including a fire load calculation. The placement of the camera or cameras results from the application environment of the customer.
  • Page 17: Maximum Distances

    AVIOTEC IP starlight 8000 Planning | en 11.26 12.12 12.99 13.86 14.72 15.59 16.45 17.32 Table 4.1: Minimum distance to fire Maximum distances Maximum distances Maximum distance to fire Fire width The tables below demonstrate exemplarily the maximum distances to a fire depending on fire...
  • Page 18: Image Margin Area

    | Planning AVIOTEC IP starlight 8000 Fire width [m] 12.6 19.2 25.1 21.0 32.0 41.9 42.1 64.1 83.9 84.3 128.3 167.8 Maximum distance to fire in m (Smoke detection) Opening angle [°] Smoke width [m] 12.8 16.7 14.1 21.4 27.9...
  • Page 19 AVIOTEC IP starlight 8000 Planning | en Figure 4.1: Definition of margin areas of the picture Horizontal margin area Vertical margin area Corner area The following table shows exemplarily the deviation in percent from the maximum detection distances at the middle of the picture:...
  • Page 20: Immediate Environment Of The Camera

    Interfering influences, e.g. high radiation – Vibrations 4.4.1 Illumination and brightness AVIOTEC IP starlight 8000 needs a minimum illumination of 7 lx. Generally, a well illuminated monitoring area is advantageous. Smoke plume and backlight Smoke plume without backlight Backlight should be avoided.
  • Page 21: Installation

    AVIOTEC IP starlight 8000 Installation | en Installation Notice! Do not expose the image sensors to direct sunlight. Do not obstruct the free flow of air around the camera. Notice! Avoid backlight. Backlight can disturb the video-based fire detection algorithm.
  • Page 22 | Installation AVIOTEC IP starlight 8000 To attach the lens to the camera: Remove the sensor protection cap from the camera. Remove the protection cap from the lens. Screw the lens onto the camera. Plug the lens connector into the camera (it automatically detects the type of lens).
  • Page 23 AVIOTEC IP starlight 8000 Installation | en DC iris lens Drive + Drive - Bosch Sicherheitssysteme GmbH Operation Manual 2016.02 | 1.0 | F.01U.318.200...
  • Page 24: Camera Mounting

    | Installation AVIOTEC IP starlight 8000 Camera mounting Mounting variants Due to the provided mounting bracket, the camera can be easily mounted. There are three main mounting variants to install the camera. Figure 5.1: Mounting variants Ceiling mount Wall mount...
  • Page 25 AVIOTEC IP starlight 8000 Installation | en focal length focus The field of view must be set manually according to the following steps: Manually adjust the focal length on the lens to obtain the required field of view. Manually adjust the focus on the lens to obtain the sharpest image possible.
  • Page 26: Wiring Of The Camera

    | Installation AVIOTEC IP starlight 8000 Wiring of the camera Connection to Ethernet via PoE Ethernet cable Notice! Use only PoE approved devices. The camera is intended to be powered via a STP Category 5e cable in a Power-over-Ethernet (PoE) network environment .
  • Page 27 AVIOTEC IP starlight 8000 Installation | en Caution! The Low Voltage power supply unit must comply with EN/UL 60950. The power supply must be a SELV-LPS unit or a SELV - Class 2 unit (Safety Extra Low Voltage - Limited Power Source).
  • Page 28: Camera Integration

    | Camera integration AVIOTEC IP starlight 8000 Camera integration The video-based fire detection can be easily integrated into the network environment of the customer. There are several possibilities to connect the camera. Various combinations are possible. The individual customer network properties determine the performance and scalability of the system.
  • Page 29: Local Area Network

    AVIOTEC IP starlight 8000 Camera integration | en Fire alarm control panel, e.g. FPA-5000 or FPA-1200 Mobile devices Local Area Network Due to the IP-based camera, the integration of the video-based fire detection into the network of the customer is easy. There are a lot of opportunities regarding to scalability and enlargement of the network.
  • Page 30: Monitoring Center

    In a monitoring center, alarms can be verified to call the fire brigade and to take care of additional rescue measures. Fire Alarm Control Panel AVIOTEC IP starlight 8000 can be connected to the a fire alarm control panel. The alarm will be triggered by the relay output of the camera. 2016.02 | 1.0 | F.01U.318.200...
  • Page 31 AVIOTEC IP starlight 8000 Camera integration | en The alarm contact assignment is shown in the figure below: 5 mm (0.2 in) MENU CVBS Alarm 4 5 6 1 2 3 Alarm socket Alarm in 1 Ground Bosch Sicherheitssysteme GmbH Operation Manual 2016.02 | 1.0 | F.01U.318.200...
  • Page 32 | Camera integration AVIOTEC IP starlight 8000 Alarm socket Alarm in 2 Ground Alarm socket Alarm out The maximum wire diameter is AWG 22-28 for both stranded and solid; cut back 5 mm (0.2 in) of insulation. Alarm out Use the alarm output for switching external devices such as lamps or sirens.
  • Page 33: Mobile Devices

    AVIOTEC IP starlight 8000 Camera integration | en EN54 2k2/3k9 input ALARM See the documentation of the individual manufacturer for further information about the connection to a fire alarm control panel. Mobile Devices Another advantage of the network integration of the video-based fire detection is the expandability to mobile devices, such as tablets or smartphones.
  • Page 34 | Camera integration AVIOTEC IP starlight 8000 2016.02 | 1.0 | F.01U.318.200 Operation Manual Bosch Sicherheitssysteme GmbH...
  • Page 35: Access Via Web Interface

    AVIOTEC IP starlight 8000 Access via web interface | en Access via web interface The unit must have a valid IP address and a compatible subnet mask to operate on your network. In a network with a DHCP server the IP address will be assigned to the camera. With no DHCP server the default address is 192.168.0.1.
  • Page 36: Detection Settings

    | Detection settings AVIOTEC IP starlight 8000 Detection settings The detection settings of the fire detection can be changed in the configuration menu: Go to Configuration and navigate to Alarm. Select Fire Detection. General and special settings for Fire detection are selectable.
  • Page 37: Masking

    AVIOTEC IP starlight 8000 Detection settings | en Masking Customized areas can be defined in the picture of the camera. These individual masks for flame and smoke detection deactivation allow individual adoption to the application of the customer. 8.2.1 Mask Masks in which the detection will be deactivated can easily be added to the picture area.
  • Page 38: Troubleshooting

    Camera If a fault cannot be resolved, please contact your supplier or system integrator, or go directly to Bosch Security Systems Customer Service. The version numbers of the internal firmware can be viewed on a service page. Please note this information before contacting Customer Service.
  • Page 39 Two LEDs (green and orange) beside the network connection indicate the LAN and PoE status No OSD messages appear. Bosch’s Video SDK is required. Video management software from third parties does not use the SDK. The ping command can be used to check the connection between two IP addresses. This allows testing whether a device is active in the network.
  • Page 40: Maintenance

    | Maintenance AVIOTEC IP starlight 8000 Maintenance 10.1 Cleaning It is generally sufficient to use a dry cloth for cleaning, but a moist lint-free cloth or leather shammy may also be used. Do not use liquid cleaners or aerosol cleaners.
  • Page 41: Technical Data

    AVIOTEC IP starlight 8000 Technical data | en Technical data Environmental Operating Temperature -20°C to +50°C (-4°F to 122°F) Storage Temperature -30°C to +70°C (-22°F to +158°F) Operating Humidity 20% to 93% RH Storage Humidity up to 98% RH Input/output...
  • Page 42 | Technical data AVIOTEC IP starlight 8000 Network Protocols IPv4, IPv6, UDP, TCP, HTTP, HTTPS, RTP/RTCP, IGMP V2/V3, ICMP, ICMPv6, RTSP, FTP, Telnet, ARP, DHCP, APIPA (Auto- IP, link local address), NTP (SNTP), SNMP (V1, MIB-II), 802.1x, DNS, DNSv6, DDNS (DynDNS.org, selfHOST.de, no- ip.com), SMTP, iSCSI, UPnP (SSDP), DiffServ (QoS), LLDP,...
  • Page 43: Appendices

    AVIOTEC IP starlight 8000 Appendices | en Appendices 12.1 Maximum detection distances for margin areas Due to the optical distorsion of the lens, there are deviating maximum detection distances at the margin area of the picture. Figure 12.1: Definition of margin areas of the picture...
  • Page 44: Flame Detection

    | Appendices AVIOTEC IP starlight 8000 12.1.1 Flame detection Opening angle 100° Fire width (m) 11.01 m 7.59 m 6.19 m 14.68 m 10.12 m 8.26 m 18.34 m 12.65 m 10.32m 22.01 m 15.18 m 12.39 m 25.68 m 17.71 m...
  • Page 45 AVIOTEC IP starlight 8000 Appendices | en 102.44 m 77.12 m 65.94 m 2.75 112.68 m 84.83 m 72.54 m 122.93 m 92.54 m 79.13 m Opening angle 60° Flame width (m) 18.29 m 16.36 m 15.44 m 24.39 m 21.82 m...
  • Page 46: Smoke Detection

    | Appendices AVIOTEC IP starlight 8000 162.83 m 152.76 m 147.72 m 2.25 183.18 m 171.85 m 166.19 m 203.53 m 190.95 m 184.65 m 2.75 223.89 m 210.04 m 203.12 m 244.24 m 229.13 m 221.58 m 12.1.2 Smoke detection Opening angle 100°...
  • Page 47 AVIOTEC IP starlight 8000 Appendices | en 1.25 34.15 m 25.71 m 21.98 m 40.98 m 30.85 m 26.38 m 1.75 47.81 m 35.99 m 30.77 m 54.63 m 41.13 m 35.17 m 2.25 61.46 m 46.27 m 39.57 m 68.29 m...
  • Page 48 | Appendices AVIOTEC IP starlight 8000 48.63 m 45.62 m 44.12 m 54.04 m 50.69 m 49.02 m 1.25 67.54 m 63.37 m 61.28 m 81.05 m 76.04 m 73.53 m 1.75 94.56 m 88.71 m 85.79 m 108.07 m 101.39 m...
  • Page 49: Index

    AVIOTEC IP starlight 8000 Index | en Index algorithm, 12 monitoring area, 9, 10 field of view, 9 Video Management System, 15 focal length, 9 Illumination, 8 Intelligent Video Analysis, 15 Bosch Sicherheitssysteme GmbH Operation Manual 2016.02 | 1.0 | F.01U.318.200...
  • Page 52 Bosch Sicherheitssysteme GmbH Robert-Bosch-Ring 5 85630 Grasbrunn Germany www.boschsecurity.com © Bosch Sicherheitssysteme GmbH, 2016...

This manual is also suitable for:

Fcs-8000-vfd-b

Table of Contents