156
en | Troubleshooting
2.
P
–
Condition:
A repeater is in tamper condition (e.g. when someone removes the device from its base or
pulls it out of the wall) if a wireless module is enabled.
Restore:
4
Supervise:
1.
2.
P
8 - External Failure
–
Condition:
A fault contact (direct connected to the zone) is triggered (zone type = external fault).
Restore:
4
Supervise:
1.
2.
P
2015.05 | 06 | F.01U.309.277
Slow flash FAULT indicator (refer to Keypad Indicators, page 8 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
RF Repeater Tamper
Restore the repeater and reset the tamper condition. For more information refer to RF
Devices, page 83.
Report repeater tamper fault to configured destination when the fault is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 8 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
External Fault Zone 1-16
Restore the fault contact and reset the fault.
Report the fault condition to configured destination on address 124 when the fault
condition is detected.
Slow flash FAULT indicator (refer to Keypad Indicators, page 8 for a detailed description).
When the fault is reset, send the restored report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
Installation Manual
AMAX panel
Bosch Sicherheitssysteme GmbH