Grounding The Drive - ABB ACS2000 AFE 1MVA User Manual

Medium voltage drives
Table of Contents

Advertisement

CHAPTER 2 – POWER ELECTRONICS AND CABINET FEATURES
Grounding the drive is only possible after the main
References
power supply has been disconnected and the DC
link has discharged. When the voltage is below 50 V

2-10 Grounding the drive

(DC), press the pushbutton
Unlocked
ment door (the pushbutton lights up) and - at the
same time - turn the grounding switch to the posi-
tion grounded
When the grounding switch is in position
grounded, the door safety switch of the AFE-INU
compartment will be released and the door can be
opened.
1
2-10
Grounding Switch
(2-10: 1)
located on the control compart-
(2-10:
2).
2
Grounding switch
40