CHAPTER 2 – POWER ELECTRONICS AND CABINET FEATURES
2.2 Power supply configurations
The drive requires two independent power supplies:
Main power supply for the power electronic
References
components
Auxiliary power supply for the control and cool-
2-1 Drive overview with
input transformer
ing equipment
2-2 Single-line diagram of
direct-to-line
2.2.1 Main power supply configurations
configuration
Input transformer
The main power is fed to the drive by the input iso-
lation transformer which adapts the line voltage to
the required voltage for the drive. The input isola-
tion transformer is always part of the drive system.
Two installation solutions are available for the
transformer:
Auxiliary
power supply
Main
power supply
MCB
2-1
1
Main
power
supply
2-2
Control and cooling equipment
Auxiliary
power
distribution
Power electronic components
Input
transformer
IFU
ACS2000
Integrated
The transformer is placed on the left side of the
drive. The length of the cabinet depends on
drive power. For the integrated configuration, a
dry-type transformer is used.
Non-integrated
The transformer is external to the drive. The
transformer can either be an oil-immersed or
dry-type device. The distance between drive
and transformer is determined by the maximum
possible cable length for the transformer sec-
ondary cables.
Drives with a non-integrated transformer are
equipped with a common mode choke.