ABB ACS2000 AFE 1MVA User Manual page 60

Medium voltage drives
Table of Contents

Advertisement

CHAPTER 3 – CONTROL SYSTEM
Table 3-7 Example for digital input signal allocation
Terminal
Channel
X11-1
DI01
X11-2
X11-3
DI02
X11-4
X11-5
DI03
X11-6
X11-7
DI04
X11-8
X11-9
DI05
X11-10
X12-1
DI06
X12-2
X12-3
DI07
X12-4
X12-5
DI08
X12-6
X12-7
DI09
X12-8
X12-9
DI10
X12-10
X13-1
DI11
X13-2
X13-3
DI12
X13-4
X13-5
DI13
X13-6
X13-7
DI14
X13-8
X13-9
+24 V
+0 V
X13-10
* Not configurable
Default setting
External start / stop request
Common
Forward / reverse
Common
Freely programmable
Common
Ramp 1 / 2
Common
Ext1 / Ext2
Common
Constant speed select
Common
External ON request (start DC link charge)
Common
Process stop (stops drive)
Common
MV switchgear open
Common
MV switchgear closed
Common
MV switchgear available (not tripped)
Common
Remote reset
Common
External OFF request
Common
Disable local operation
Common
24 V control logic
Common
60
Parameter group
72.06 – 72.09
72.10 – 72.11
72.41 – 72.42
30 – 31
24 – 25
72.02 – 72.03
72.43 – 72.44
*
*
*
72.33 – 72.34
72.04 – 72.05
72.35 – 72.36

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents