CHAPTER 10 – PREVENTIVE AND CORRECTIVE MAINTENANCE
11. When all cables have been reconnected, check
that the drive control system and the phase
module communicate with each other. Switch
on the auxiliary power supply.
Check that the LEDs on the
board
of the phase module are on (box).
12. Push the phase module back into the rack as far
as it goes and tighten the fastening bolt on
each side.
13. Remove the rails and reinstall the acrylic panel.
14. Switch on all miniature circuit breakers in the
control compartment.
The work is now completed, and the drive can be
started again.
For further information, see
10.6.13 Replacing a fan
The fan housing can stay on the roof when only the
impeller is replaced.
1. Disconnect all power supplies to the drive and
ground the drive.
For further information, see
ing the drive
locally.
To isolate the fan unit from the auxiliary power
supply, switch off the motor starter of the fan
unit.
To identify the motor starter, see Appen-
dix D – Wiring diagrams.
2. Continue with
Standard fan units
units
as applicable.
Standard fan units
3. Remove the cover from the fan housing.
4. Disconnect the control and power supply cables
of the fan.
5. Remove the fastening screws from the support
Support plate
Phase-INT circuit
6. Using the lifting eyes in the fan housing cover
8.6 Starting the
drive.
7. Unscrew the support plate from the fan
10.6.3 De-energiz-
8. Replace the fan and re-assemble in reverse
DTL fan units
9. Disconnect the power supply cable at the entry
10. Unscrew the cover from the fan housing.
Disconnect here
or
DTL fan
plate and the duct ring.
Duct ring
and a lifting gear, lift off the support plate with
the fan attached to it.
order of removal.
of the terminal box.
Terminal box