ABB ACS2000 AFE 1MVA User Manual page 170

Medium voltage drives
Table of Contents

Advertisement

CHAPTER 10 – PREVENTIVE AND CORRECTIVE MAINTENANCE
10.6.10 Checking wire and cable connections
Vibration can loosen electrical connections and
cause occasional malfunction or equipment failure.
Check all power and control cable connections
and tighten them if necessary.
Check that all plugs and connectors are tight.
NOTICE
Capaci tor bushi ngs ar e dam aged w hen excessi ve
f or ce i s appl i ed.
D o not exceed the m axi m um ti ghteni ng tor que.
The ti ghteni ng tor que val ue i s pri nted on a l abel
w hi ch i s attached to the capaci tor . I f not speci fi ed,
the m axi m um ti ghteni ng tor que m ust not exceed
20 N m .
10.6.11 Replacing filter mats
References
10-12 Replacing filter
mats
To replace a filter mat:
1. Unfasten the air intake panel upper supports
(1).
2. Remove the air intake panel
3. Remove the filter mat
compressed air or a vacuum cleaner. Perform
this operation away from the drive to prevent
dust from entering.
Filter class
(EN779 classification)
Dimensions
1. Supports
2. Air intake panel
3. Filter mat
10-12
For information on replacement intervals,
see the ACS2000 preventive mainte-
nance schedule.
(2).
(3)
and clean it by using
Standard
Option
G3
G4
layout
See
See
drawing
drawing
1
2
Thickness
layout
1
3
Standard
Option
10 mm
20 mm
170

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents