ABB ACS2000 AFE 1MVA User Manual page 129

Medium voltage drives
Table of Contents

Advertisement

129
ACS2000 AFE 1MVA UM 3BHS297030 ZAB E01 REV. J
emergency-off switch linked to the drive, is
pressed. If the EMERGENCY RESET pushbutton
continuous flashing, verify that there is no
emergency-off command active.
For further information, see
4. Check that no alarm or fault messages are dis-
played on the CDP control panel.
When a fault message is displayed on the CDP
control panel, reset the fault.
If a fault cannot be reset, it must be rectified by
the responsible personnel.
For further information, see
indications.
When no alarms and faults are present and the
drive is ready, the CDP control panel displays
ReadyOn.
5. Press the
trol compartment door to close the MCB and
charge the DC link. The
The status line of the CDP control panel alter-
nates between Charging and AuxiliaryOn.
1 L ->
StateINU
MOTOR SP
POWER
After charging has finished,
modulate.
When the AFE is in ReadyRef state, the state of
the INU changes to ReadyRun and the motor
can be started.
8.8
10.3 Alarm / fault
1 L ->
0.0 rpm
ReadyOn
StateINU
MOTOR SP
0.00 rpm
POWER
0.0 kW
SUPPLY ON pushbutton
pushbutton lights up.
0.0 rpm
Charging
0.00 rpm
0.0 kW
the AFE starts to
If the CDP control panel was switched to the
AFE, you would first see the message Modu-
lating and then after a short instant the
message ReadyRef in the status line of the
display.
1 L ->
0.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
6. Enter the reference value.
For further information, see
reference
Emergency-off.
1 L ->
StateINU
MOTOR SP
POWER
7. Start the motor.
When the motor has been magnetized, the
motor speed ramps up to the reference value.
While the motor is accelerating, the run status
message on the display blinks. When the motor
speed has reached the reference value, the run
status message lights up permanently.
To indicate that the drive is operating, the dis-
play shows ReadyRef.
1 L ->
StateINU
on the con-
MOTOR SP
POWER
Charging
AuxiliaryOn
9.10.2 Entering a
value.
[600.0 rpm] 0
ReadyRun
0.00 rpm
0.0 kW
600.0 rpm
ReadyRef
0.00 rpm
1000.0 kW