10.4 Removing the CDP control
panel
1. When the panel is removed while the drive is in
operation, check the setting of parameter 31.01
PANEL LOSS SUPERVISION first.
If the parameter is set to NOT USED, the panel
can be removed without interrupting drive
operation.
—
When the CDP control panel has
been removed during operation,
the drive can only be stopped by
pressing the emergency-off but-
ton.
For information on setting parameters,
see Appendix G – Signal and parameter
table.
1
1 L ->
1242,0 rpm
StateINU
ReadyOn
MOTOR SP
1242 rpm
POWER
86.0 kW
2. To remove the panel, proceed as illustrated.
2
1
Meaning of the LEDs
The green LED
[4]
signals that the control voltage
has been switched on.
Communication with AMC circuit board
The CDP control panel
(1)
is connected to the AMC
circuit board of the INU
(2)
RS485-Interface.
2
3
3
4
and the AFE
(3)
via an