CHAPTER 10 – PREVENTIVE AND CORRECTIVE MAINTENANCE
Replacing a phase module
1. Disconnect all power supplies to the drive and
ground the drive.
For further information, see
ing the drive
locally.
DANGER
!
Hazardous voltages!
When a phase module is removed from the cabinet,
the grounding path between grounding switch and
PE ground busbar is interrupted.
For this reason, connect grounding equipment at
the appropriate locations. The grounding
equipment ensures that hazardous voltages
cannot be fed into the drive from the main power
supply or the motor.
2. Remove the appropriate acrylic panel.l
Note: When working on the AFE, pull out the air
pressure tube at the bottom
below).
1
3. Remove the screws on each side of the phase
module.
10.6.3 De-energiz-
4.
Slide the module rails under the phase
10 mm
!
To prevent the phase module from dropping on
you, make sure the rails are slid completely under
(see 1 in the figure
the phase module.
5. Holding the phase module at the handles, pull it
out carefully.
225 mm
CAUTION
172
13 mm
module.
.