ACQ800-37 Hardware Manual

Fault tracing

Faults and warnings displayed by the CDP-312R Control Panel

The control panel will display the warnings and faults of the unit (i.e. supply unit or
inverter unit) the panel is currently controlling.
The warnings and faults concerning the inverter unit (motor-side converter) are dealt
with in the inverter control program (e.g. Pump Control Program) Firmware Manual.

Warning/Fault message from unit not being monitored by control panel

Flashing messages WARNING, ID:2 or FAULT, ID:2 on the control panel display
indicate a warning or fault state in the line-side converter when the panel is
controlling the motor-side converter:
FAULT, ID:2
ACQ 800 0460_5MR
*** FAULT ***
LINE CONV
To display the warning or fault identification text, switch the control panel to view the
line-side converter as described in section

Conflicting ID numbers

If the ID numbers of the line-side and the motor-side converters are set equal, the
control panel stops functioning. To clear the situation:
• Disconnect the panel cable from the RMIO board of the motor-side converter.
• Set the ID number of the line-side converter RMIO board to 2. For the setting
procedure, see the inverter control program (e.g. Pump Control Program)
Firmware Manual.
• Connect the disconnected cable to the RMIO board of the motor-side converter
again and set the ID number to 1.
(FF51)
Control panel
on page 38.