6.3.2 Hysteresis setting
esis.
ENT
ENT
To close "Hysteresis Setting"
To close the "Hysteresis Setting" or cancel
the mode midway, press the
A previous screen will return.
Setting range
0 to 20% of full scale
[% full scale (% FS)] represents the
percentage with the width of the component
measurement range regarded as 100%.
Hysteresis (In case of upper limit alarm)
Hysteresis
width
Alarm
Contact output
-
Alarm Setting
key
ESC
key.
36
Set Hysteresis
0 to 20%FS available
Alarm-1
Alarm-2
Alarm-3
Alarm-4
Alarm-5
Hysteresis
0
0
%FS
(
End of Hysteresis Setting
CAUTION
The hysteresis is common to all alarms
(components).
Hysteresis in peak alarm setting
described in Section 6.3.3 should be set
separately.
Upper limit value
ON (closed)
OFF (open)
-
ENT
)
-
INZ-TN2ZPB-E