AS-i 3.0 PROFINET Gateway in Stainless Steel
Configuration of AS-i/PROFINET Gateways
10.5

Safety Control/Status

In the fieldbus configuration the designator Safety Control/Status can be added
as cyclical data. This is possible both for the integrated Safety Monitor and for 2nd
generation Monitors.
Information!
Generation III external Monitors allow a maximum of eight OSSDs to be sent.
The state of the outputs and the message outputs is then inserted as a cyclical in-
put datum.
Inputs
byte
description
1
Status OSSD 1, color-coded as defined in the table <Coding of status
bytes>).
2
Status OSSD 2, color-coded as defined in the table <Coding of status
bytes>).
...
...
n
Status OSSD n, color-coded as defined in the table <Coding of status
bytes>).
Coding of status bytes
Bit [0 ... 3]
00
16
01
16
02
16
03
16
04
16
05
16
06
16
07
16
Bit [6]
0
1
state or. color
green permanent ligh-
ting
green flashing
yellow permanent ligh-
ting
yellow flashing
red permanent lighting
red flashing
grey or off
reserved
status or color
no device flashing yel-
low
at least one device flas-
hing yellow
description
output on
delay time is running at stop category 1
start-up/restart-disable active
external test necessary / acknowledge-
ment / start delay active
output off
error
output not projected
Tab. 10-24.
Tab. 10-25.