AS-i 3.0 PROFINET Gateway in Stainless Steel
Advanced Diagnostics for AS-i Masters
or on a sensor line.
The menu EFLT Ratio shows the asymmetry of the AS-i network, referenced to
ground (see sketch).
9.5.4

Current can be read directly on the unit

Now the devices display both the maximum current and the current actually pre-
sent in the respective AS-i circuit. Heavy consumers or a strong overload in an
AS-i circuit are then easy to detect. Plus you can set the maximum current in the
AS-i circuit on these devices. This ensures line protection even when using large
24V power supplies.
38
1.
Earth fault sen.
100%
%
0%
%
100%
EFLT Ratio:
AS-i+ 2%
AS-i DC Voltage: 1
31,3V
EFLT Ratio:
AS-i+ 100%
AS-i DC Voltage: 2
31,5V
AS-i power
Reset
Maximal:
1,3A
AS-i +
AS-i -
#
$
#
2
"