Pepperl+Fuchs AS-I 3.0 PROFINET Manual page 65

Table of Contents

Advertisement

AS-i 3.0 PROFINET Gateway in Stainless Steel
Codes indicated by the display
79
Checksum error in the data menu.
"breakpoint":
Control III C program in break point.
80
Error while attempting to exit the configuration mode: A slave with address
zero exists.
81
General error while changing a slave address
82
The front panel operation is blocked. Until repowering-up the device can only
be accessed from the host via the interface.
83
Program reset of the AS-i Control program: The AS-i Control program is being
read from the EEPROM and copied into the RAM.
88
Display test while starting up the AS-i master
90
Error while changing a slave address in protected operating mode: No slave
with address 0 existing.
91
Error while changing slave address: Target address is already used.
92
Error while changing slave address: New address could not be set.
93
Error while changing slave address: New address could only be stored volatile
in the slave.
94
Error while changing the slave address in protected operating mode: Slave
has wrong configuration data.
95
The error 95 is caused by a superfluous slave and not by a missing slave.
That is why the slave address is occupied by this superfluous slave.
(In the protected mode the slave addresses which caused any configuration
error can be displayed by pressing the SET button. AS-i master without gra-
phical display are not able to differentiate between a missing slave, an incor-
rect slave or a redundant slave. All incorrect addresses are displayed.
By pressing the SET button 5 sec. the displayed address starts to flash. Pres-
sing the SET button again the master attempts to program the slave at the
address 0 to the incorrect address.)
65

Advertisement

Table of Contents
loading

Table of Contents