Programming

POTS Settings

COMMUNICATOR
1=INSTALLED
2=POTS SETTINGS
3=IP SETTINGS
Communicator Screen #1
POTS Line (X)
If telephone lines are connected to the IPOTS-COM board at J4 (Line 1) and J5 (Line 2), their settings can be configured by pressing 1
or 2, respectively. Pressing 1 or 2 will display the following screen. The programming options for Line 1 and Line 2 are identical.
Phone Line (X) Enable
To enable the phone line, press 1 while viewing the POTS Line (X) Screen #1 to change the display to Enabled Yes. Each press of the 1
key will cause the display to toggle between Enabled Yes and Enabled No.
Type
POTS LINE X
1=ENABLED
2=TYPE
3=SUPERVISED
POTS Line X Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33 or 3 to select Rotary dialing with a
make/break ratio of 60/40.
Supervised Phone Line
POTS LINE X
1=ENABLED
2=TYPE
3=SUPERVISED
POTS Line X Screen
table on page 46 for permissible settings.
Gains
POTS SETTINGS
1=LINE 1
2=LINE 2
3=GAINS
POTS Settings Screen
The Gains value can be adjusted for when the telephones lines are in use for Dialing and Reporting. Press 1 or 2 to change these values,
respectively. The following screen will display for both options.
Press 1 for Low, 2 for Normal, and 3 for High. After the Gains value has been selected, the display will return to the Gains Screen.
78
The POTS settings configure the system when telephone lines are used to contact central station. Pressing 2
NO
while viewing the Communicator Screen #1 will display the following.
To select the type, press 2 while viewing the POTS Line (X) Screen #1. The following screen will be dis-
played:
YES
YES
The Supervised Phone Line feature allows the user to disable the supervision of Phone Lines when using an
YES
alternate means of secondary transmission path. The factory default setting is Phone Line (X) super-
vised.Supervision must be set to Yes if the selected transmission path is POTS.
YES
Pressing 1 for Supervision while viewing the POTS Line (X) Screen #2 will change the screen to read
Supervision No. Each press of the 1 key will toggle the option between Supervise Yes and No. Refer to the
The Gains value is the telephone's transmitting "volume control". To adjust the settings, press 3 while
viewing the POTS Settings screen. The following screen will be displayed:
POTS SETTINGS
1=LINE 1
2=LINE 2
3=GAINS
POTS Settings Screen
POTS LINE X
1=ENABLED
YES
2=TYPE
TOUCHTONE
3=SUPERVISED
YES
POTS Line X Screen
TYPE
1=TOUCHTONE
2=ROTARY 67/33
3=ROTARY 60/40
Type Settings Screen
GAINS
1=DIALING
NORM
2=REPORTING
NORM
Gains Screen
GAINS
1=LOW
2=NORMAL
3=HIGH
Gains Screen