Programming
Zones 047, 048, 049, and 046 can be programmed for normal zone operation or for special purpose applications. In the above illustra-
tion, the four zones are shown Off, which means they can be programmed to function in the same manner as all other zones, by assigning
them to input and output devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 47 On. Each press of the 1 key will cause the display to toggle between PAS 47 On and
PAS 47 Off. When Zone 047 is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke detector will cause Zone 047
to activate. By assigning Zone 047 to a control module in the Programming Zone Assignment Screen, an output device connected to the
control module can be used to indicate a PAS condition in the control panel. Do not assign Zone 047 to a Notification Appliance Circuit
when using this zone to indicate a PAS condition. Attempting to do so will generate an error message and will be prevented by software
checks.
Pressing 2 will cause the display to change to Pre-signal 48 On. Each press of the 2 key will cause the display to toggle between Pre-sig-
nal 48 On and Pre-signal 48 Off. When Zone 048 is programmed On, a Pre-signal activation of any device will cause Zone 18 to acti-
vate. By assigning Zone 048 to a control module in the Programming Zone Assignment Screen, an output device connected to the
control module can be used to indicate a Pre-signal condition in the control panel. Do not assign Zone 048 to a Notification Appliance
Circuit when using this zone to indicate a Pre-signal condition. Attempting to do so will generate an error message and will be prevented
by software checks.
Pressing 3 will cause the display to change to Two Stage 49 On. Each press of the 3 key will cause the display to toggle between Two
Stage 49 On and Two Stage 49 Off. Refer to "Two Stage Operation" on page 74 for a description of this feature.
Pressing 1 while viewing the Special Purpose Zone Screen #2 will cause the display to change to Local Alm 46 On. Each press of the 1
key will cause the display to toggle between Local Alm 46 On and Local Alm 46 Off. When Zone 46 is programmed On, a Local Alarm
activation of any smoke detector will cause Zone 046 to activate. By assigning Zone 046 to a control module in the Programming Zone
Assignment Screen, an output device connected to the control module can be used to indicate a local alarm condition in the control
panel. Local Alarm Zone alarms are not reported to the Central Station.

Zones Installed

ZONE SETUP
1=ZONES INSTALLED

2=ZONES ENABLED

3=ZONES DISABLED

Zone Setup Screen #2
This display will show all of the zones that have been programmed into the control panel. Note that an up and/or down arrow may appear
in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to
view the additional zones.
Zones Enabled
Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to the following:
This display will show all of the zones that are enabled in the control panel. Note that an up and/or down arrow may appear in the upper
right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the
additional zones.
Zones Disabled
Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar to the following:
This display will show all of the zones that are disabled in the control panel. Note that an up and/or down arrow may appear in the upper
right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view the
additional zones.
66
Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to the fol-
lowing:
ZONES INSTALLED
000 001 002 003 004
005
Zones Installed Screen
ZONES ENABLED
000 001 002 004 005
006 007 008 009 010
011 012 013 014
Zones Enabled Screen
ZONES DISABLED
003
Zones Disabled Screen
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Master Programming Level