Power Supply Calculations
Device Type
1
Main Circuit Board
IPOTS-COM Communicator
CELL-MOD/CAB-N
N-ANN-80
N-ANN-100
N-ANN-(R)LED
N-ANN-RLY
N-ANN-I/O
N-ANN-S/PG
4XTM
4-wire Detector Heads
4
Power Supervision Relays
NI-100, FSI-851
NP-100, NP-200,
FSP-851, FSP-951
NP-100T, NP-200T,
FSP-851T, FSP-951T
NP-A100, FAPT-851
NH-100, NH-200,
FST-851, FST-951
NH-100R, NH-200R,
FST-851R, FST-951R
NH-100H, NH-200H,
FST-851H, FST-951H
ND-100, FSD-751PL
ND-100R, FSD-751RPL
5
B501BH & B501BHT
B224RB
B224BI
NMM-100, FMM-1
XP10-M
NDM-100, FDM-1
NMM-100P, FMM-101
NZM-100, FZM-1
NZM-100-6, XP6-MA
NOT-BG-12LX, NBG-12LX
NC-100/FCM-1
XPC-6
NC-100R/FRM-1
XPR-6
N-100ISO, ISO-X
ISO-6
FWSG
7
NAC #1
7
NAC #2
FCPS (remote sync)
Current Draw from TB3
Sum each column for totals
1 Main board with display only.
2 If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another 0.005 amps.
3 Refer to the Device Compatibility Document for standby current.
4 Must use compatible listed Power Supervision Relay.
5 Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source.
6 When powered by an external source, use 0.040A. When powered by the SLC, use 0.024A.
126
Calculation Column 1
Primary (AC) Power Source
Fire Alarm Current (amps)
Qty
X[current draw]=
[
]
X[0.041]=
[
]
X[0.100]=
[
]
X[0.040]=
[
]
X[0.025]=
[
]
X[0.068]=
[
]
X[0.075]=
[
]
X[0.200]=
[
]
X[0.045]=
2
[
]
X[0.011]
=
[
]
X[
]=
[
]
X[0.025]=
maximum alarm draw
for all devices =
[
]
X[
]=
[
]
X[
]=
[
]
X[0.02]=
[
]
[
]=
AC Powered,
8
Fire Alarm Load
=
Table 9.3 System Current Load Calculations
Calculation Column 2
Secondary (Battery) Power Source
Fire Alarm Current (amps)
Total
Qty
X [current draw]=
1
X[0.257]=
[
]
X[0.041]=
[
]
X[0.100]=
[
]
X[0.040]=
[
]
X[0.025]=
[
]
X[0.068]=
[
]
X[0.075]=
[
]
X[0.200]=
[
]
X[0.045]=
[
]
X[0.011]=
[
]
X[
]
[
]
X[0.025]=
maximum alarm draw
0.200
for all devices =
[
]
X[
[
]
X[
[
]
X[0.0217]=
[
]
[
]=
Battery Powered,
9
Fire Alarm Load
=
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Calculating the System Current Load
Calculation Column 3
Secondary (Battery) Power Source
Standby Current (amps)
Total
Qty
X [current draw]=
1
[
]
[
]
[
]
[
]
[
]
[
]
[
]
[
]
[
]
3
=
[
]
[
]
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
X[0.00030]=
[
]
[
]
X[0.00050]=
0.200
[
]
X[0.00045]=
[
]
X[0.00040]=
[
]
X[0.00350]=
[
]
X[0.00075]=
[
]
X[0.000375]=
[
]
X[0.00027]=
[
]
X[0.00200]=
[
]
X[0.00030]=
[
]
X[0.00039]=
[
]
X[0.00225]=
[
]
X[0.00027]=
[
]
X[0.00145]=
[
]
X[0.00040]=
[
]
X[0.00045]=
[
] X[0.040] or [0.024]
]=
]=
[
]
Battery Powered,
Standby Load
Total
X[0.141]=
X[0.040]=
X[0.055]=
X[0.015]=
X[0.020]=
X[0.028]=
X[0.015]=
X[0.035]=
X[0.045]=
X[0.005]=
X[
]=
X[0.025]=
X[0.001]=
6
[
]=
10
=