Master Programming Level
The Communication Format is determined by the type of receiver that the Communicator is transmitting to. Consult your Central Station
for proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the
event codes.
Select the Communication Format by pressing the corresponding number key while viewing the Comm Format screen. The following
table describes each format:
Test Time Interval
POTS XXX COMM PATH
1=TEST TIME INT
2=24HR TEST TIME 0100
POTS Comm Path Screen #4
The test report sent to the Central Station phone number may be sent once every 6, 8, 12, or 24 hours. Select the desired Test Time Inter-
val by pressing the corresponding digit in the screens shown above. Refer to the table on page 46 for permissible settings.
24 Hour Test Time
POTS XXX COMM PATH
1=TEST TIME INT
2=24HR TEST TIME 0100
POTS Comm Path Screen #4
Use the 24 Hour Test Time screen to program the time that the Communicator will transmit the 24 Hour Test to the Central Station. A
flashing cursor will appear in the lower left corner of the screen. Enter a four digit number representing the test time using military time
(0000 = midnight and 2359 = 11:59PM).
Ethernet
XXX COMM PATH
1=POTS
2=ETHERNET
3=CELLULAR
Comm Path Screen #1
Enable
To enable the Ethernet connection, press 1 while viewing the Ethernet Options Screen #1 to change the display to Enabled Yes. Each
press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No.
Central Station Account
ETHERNET OPTIONS
1=ENABLED
2=CS ACCOUNT
Ethernet Options Screen #1
Enter the City ID, Central Station ID, and Account Code all provided by the monitoring station..
NOTE: When using Ethernet as the primary and Cellular as secondary, the three CS account codes must be the same for both paths.
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Screen Selection
ADEMCO CONTACT ID
SIA 8
SIA 20
Table 3.2 Communication Formats
Pressing 1 while viewing POTS (XXX) Comm Path #4 will cause the following screens to be displayed:
24
TEST TIME INTERVAL
1=24 HOURS
2=12 HOURS
3=8 HOURS
Test Time Interval Screen #1
Pressing 2 while viewing POTS (XXX) Comm Path #4 will cause the following screen to be displayed:
24
To configure the communication method to contact central station as an ethernet connection, select 2 for
Ethernet from the Comm Path Screen. The following screens will display.
ETHERNET OPTIONS
1=ENABLED
2=CS ACCOUNT
Ethernet Options Screen #1
Press 2 on Ethernet Options Screen #1 to display the following:
YES
Communication Format Description
Contact ID, DTMF, 1400/2300 ACK
Security Industry Association, 8 messages per call
Security Industry Association, 20 messages per call
24 HOUR TEST TIME
RANGE 0000-2359

24 Hour Test Time Screen
NO
CS ACCOUNT
1=CITY ID
0000
2=CS ID
0000
3=ACCT CODE
000000
Central Station Account Screen
TEST TIME INTERVAL
1=6 HOURS
Test Time Interval Screen #2
ETHERNET OPTIONS
1=SUPV. SETTINGS
NFPA 2010 DUAL PATH
Ethernet Options Screen #2
Programming
81