Waterflow Silenceable; Auxiliary Power; Trouble Reminder; Language - Honeywell NOTIFIER NFW-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for NOTIFIER NFW-50X:
Table of Contents

Advertisement

Programming
The F1 function key is automatically configured to perform a manual alarm signal activation when pressed.
The F2 function key is automatically configured to perform a two-stage bypass when pressed.
If NACs are set up for two-stage operation, the Silence Inhibit timer is automatically enabled and is fixed at 5 minutes.
AlarmNet supervision settings are fixed at 3 minutes and cannot be changed regardless of supervision programming selection.

Waterflow Silenceable

SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3

Auxiliary Power

SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM

3=LANGUAGE

ENGLISH
System Setup Screen #4
Select the AUX 1 output. The following screen will be displayed.
Aux 1 can be programmed for Class A wiring. If Aux 1 is to be wired for Class A, press 1. Each press of the 1 key will cause the display
to toggle between Class A Yes and Class A No.
In addition, the aux power output can be programmed as resettable or non-resettable power. Non-resettable power is suitable for power-
ing annunciators while resettable power is suitable for powering smoke detectors. Each press of the 1 key will cause the display to toggle
between Resettable Yes and Resettable No.

Trouble Reminder

SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM
3=LANGUAGE
ENGLISH
System Setup Screen #4
Language
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM
3=LANGUAGE
ENGLISH
System Setup Screen #4

Charger Enable

SYSTEM SETUP
1=CHARGER ENAB
2=4XTM SPV ENAB
3=REM SYNC ENAB
System Setup Screen #5

4XTM Supervision

SYSTEM SETUP
1=CHARGER ENAB
2=4XTM SPV ENAB
3=REM SYNC ENAB
System Setup Screen #5

Remote Sync Enable

SYSTEM SETUP
1=CHARGER ENAB
2=4XTM SUPV ENAB NO
3=REM SYNC ENAB
System Setup Screen #5
76
Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the system for
silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the display between
Waterflow Sil. No and Waterflow Sil. Yes. When Waterflow Sil. No is selected, all output devices associated
with a waterflow type input device, will be nonsilenceable. When Waterflow Sil. Yes is selected, all output
devices associated with a waterflow type input device, will be silenceable.
A Special Application 24 VDC power output is available at TB11 on the main circuit board. Pressing 1
while viewing System Setup Screen #4 displays the following:
24HR
1=AUX 1
1=CLASS A
2=RESETTABLE
The Trouble Reminder features causes the control panel piezo to sound a reminder 'beep' for alarms and
troubles, after the panel has been silenced. Refer to "Trouble Reminder" on page 68, for a detailed descrip-
24HR
tion of this feature. Pressing 2 while viewing System Setup Screen #4 will cause the display to toggle to
Trouble Rem 4 or Trouble Rem 24, which enables this feature for resound at either 4 or 24 hours, respec-
tively. Each press of the 2 key will cause the display to toggle between Trouble Rem 4 or Trouble Rem 24.
Refer to the table on page 46 for permissible settings.
The language option is used to change the text on the panel display to either English or French. Pressing the
3 key will cause the display to offer a choice of 1=English and 2=French.
24HR
If using an external battery charger, the FACP battery charger must first be disabled. Pressing 1 while view-
YES
ing System Setup Screen #5 will cause the display to toggle to Charger Enab No, which will allow the use
NO
of an external battery charger. Each press of the 1 key will cause the display to toggle between Charger
YES
Enab. No and Charger Enab. Yes.
If a 4XTM Transmitter Module is installed in the system, supervision must enabled in user programming.
YES
Pressing 2 while viewing System Setup Screen #5 will cause the display to toggle to 4XTM Supv Enab. Yes,
NO
which means there is a 4XTM installed. Each press of the 2 key will cause the display to toggle between
YES
4XTM Supv Enab. No and 4XTM Supv Enab. Yes. Refer to the table on page 46 for permissible settings.
Synchronization is a feature that controls the activation of notification appliances in such a way that all
YES
devices will turn on and off at exactly the same time. Refer to Section 2.5, "Remote Synchronization Out-
put", on page 26 for more information. To enable remote synchronization, press the 3 key while viewing
YES
System Setup Screen #5. Each press of the key will toggle the screen between Rem Sync Enab Yes and Rem
Sync Enab No.
AUX POWER
AUX 1
YES
YES
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Master Programming Level

Advertisement

Table of Contents