Programming
 Normal - indicates that the detector with the selected address is physically installed on the SLC and communicating with the
control panel (enabled)
 <ADJ><NOUN> - represents the adjective and noun, which have been programmed, describing the location of the displayed
device
 ZNNN - represents the first of five possible software zones that the detector is assigned to (NNN = the three digit zone number
from 000 - 049)
 V or * - indicates whether or not alarm verification is enabled (V = alarm verification enabled and * = alarm verification
disabled)
 W or * - indicates whether or not walktest is enabled (W = walktest enabled and * = walktest disabled)
 X or * - indicates whether or not the detector is wireless (X = wireless detector and * = wired detector)
 1D017 - represents the Loop, Device type and Device address (1=SLC Loop, D=Detector and 017=Detector Address 017)
The following examples show the editing of a photoelectric smoke detector with address 017, located on the SLC loop:
EDIT DETECTOR 1D017
1=ENABLED
2=TYPE SMOKE(PHOTO)
3=VERIFICATION
Edit Detector Screen #2
EDIT DETECTOR 1D017
WIRELESS
2=SOUNDER BASE
Edit Detector Screen #5
Enable/Disable Detector
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
Type
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
Pressing the down arrow key will display additional detector types as indicated in the following table.
52
YES
OFF
NO
To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2. Each press of
the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the detector
will not be polled by the control panel, preventing the detector from reporting alarms and troubles to the
panel. The control panel will display the device type and address which has been disabled and will turn on
the Trouble LED and Disable LED.
To select the type of detector being programmed, press the 2 key while viewing the Edit Detector Screen
#2. This will cause the control panel to display the following Detector Type Screens:
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE(ION)
Detector Type
Smoke Photo
User-Defined-1
Smoke (Ion)
User-Defined-2
Heat Detect
User-Defined-3
Smoke Duct-P
User-Defined-4
Photo w/Heat
User-Defined-5
Duct Superv
User-Defined-7
Photo Super AR
User-Defined-8
ADAPT
User-Defined-10
Fire/CO
User-Defined-12
EDIT DETECTOR 1D017
1=WALKTEST
YES
2=PAS
NO
3=PRE-SIGNAL
NO
Edit Detector Screen #3
EDIT DETECTOR 1D017
1=NOUN/ADJECTIVE
2=DESCRIPTION

Edit Detector Screen #6
through
Action When Activated
Fire Alarm
same as previous (Smoke Photo)
Fire Alarm
same as previous (Smoke Ion)
Fire Alarm
same as previous (Heat Detect)
Fire Alarm
same as previous (Smoke Duct-P)
Fire Alarm
same as previous (Photo w/Heat)
Supervisory, latching
same as previous (Duct Superv)
Supervisory, nonlatching (works only in LiteSpeed)
same as previous (Photo Super AR)
Fire Alarm
same as previous (ADAPT)
response is programmable (Alarm, Supv, or None)
same as previous (Fire/CO)
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Master Programming Level
EDIT DETECTOR 1D017
1=ZONE ASSIGNMENT
000 
Edit Detector Screen #4
DETECTOR TYPE
1=FIRE CO
2=USER-DEFINED-12