D.1: Nac Wiring - Honeywell NOTIFIER NFW-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for NOTIFIER NFW-50X:
Table of Contents

Advertisement

NAC Wiring
D.1 NAC Wiring
The following table lists NAC wiring requirements for the FACP.
NAC Load
(Amps)
0.25
0.5
0.75
1
1.25
1.5
1.75
2
2.25
2.5
Notes:
1.
Calculations are based on Direct-Current Resistance data for uncoated copper wire, per National Electrical Code (2011 Edition)
Table 8, Conductor Properties.
2.
These distances reflect the worst case scenario and are based on the current draw of the highest candela strobes at the low end of the
supported NAC voltage with the entire load at the end of the circuit. Further distances can be achieved by performing a point-to-
point voltage calculation that more accurately reflects the specific devices used and how they are dispersed on the circuit.
3.
If using Gentex brand notification appliances, the "UL Max" current rating published in their data sheets, must be used in order to
maintain performance under low battery conditions with the maximum wire resistances shown in the table above.
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Max.
Max. allowable wire pair length
allowable
total loop
resistance
AWG 12
AWG 14
(ohms)
solid
solid
14.40
4450
7.20
2225
4.80
1483
3.60
1112
2.88
890
2.40
742
2.06
636
1.80
556
1.60
494
1.44
445
Table D.2 NAC Wiring Requirements for FACP
CLASS-B
(feet)
AWG 16
AWG 18
solid
solid
2797
1756
1105
1399
878
553
932
585
368
699
439
276
559
351
221
466
293
184
400
251
158
350
220
138
311
195
123
280
176
111
CLASS-A
Max. allowable wire pair length
(feet)
AWG 12
AWG 14
AWG 16
solid
solid
solid
2225
1399
1112
699
742
466
556
350
445
280
371
233
318
200
278
175
247
155
222
140
Wire Requirements
AWG 18
solid
878
553
439
276
293
184
220
138
176
111
146
92
125
79
110
69
98
61
88
55
139