Honeywell NOTIFIER NFW-50X Manual page 40

Addressable fire alarm control panel
Hide thumbs Also See for NOTIFIER NFW-50X:
Table of Contents

Advertisement

Installation
N-
ANN-I/O Connection to FACP
The N-ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.23. After the N-ANN-I/O is connected to the panel,
it must be added to the system via FACP programming. Refer to the section titled "ANN-I/O Options" on page 87.
N-
ANN-I/O Module LED Wiring
There are four 12-pin connectors on the N-ANN-I/O module for connecting LEDs. Each set of 10 LEDs get their power from Pin 11 of
the corresponding connector. Internal resistors are sized so that there is approximately 10 mA of current for each LED. No series resis-
tors are required. LED outputs can be mapped to output circuits. Refer to the programming section titled "ANN-I/O Options" on page 87
of this manual.
The LEDs are wired as illustrated in Figure 2.24. Note that the illustration depicts only connectors P1 and P2. Wiring is identical for P3
(LEDs 21-30) and P4 (LEDs 31-40).
40
P1
P2
10
1
20 21
11
20
LED Out
LED Out
LED Power
LED Power
Not Used
Not Used
ANN-I/O Module
Primary ANN-BUS
+
-
Figure 2.23 ANN-I/O Connection to FACP
P3
P4
30
40
31
LED Out
LED Out
LED Power
LED Power
Not Used
Not Used
ANN-BUS and power wiring are
supervised and power-limited
24 VDC nonresettable
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018